Isolation Switch Handle to Contactor

Mechanical Interlock

The Limitamp AR two-high vacuum starter is equipped with a

quick-make, quick-break isolation switch in each starter. This

isolation switch is not designed to make or break motor load

current. To insure that the isolation switch handle cannot be

operated when the contactor is energized, a mechanical interlock

mechanism is provided between the contactor and the isolation

switch handle. Operation of this mechanical interlock for each

starter should be checked per the following procedure.

WARNING: Confirm the equipment is de-energized before

performing this check.

Figure 8. View of the contactor to isolation switch

mechanical interlock at the vacuum contactor.

Figure 9. Adjusting connecting rod

Step 1: Adjust the nuts to shift the connecting rod position as

shown in Figure 10.

Step 2: With the contactor open the connecting rod should be

adjusted up to a point where the pusher will pass through the

round hole in the connecting rod.

Step 3: Once adjusted tighten the two nuts against the block.

Adjustment Nuts On

the Interlock Assembly

Figure 11. Showing how pusher is blocked when the contactor

is closed.

Figure 10. Showing how pusher is unblocked when the contactor

is open.

To verify that the interlock is properly adjusted push down on

the top of the contactor moving armature and hold it down.

Now attempt to press the handle latch release (pusher). The

mechanical interlock should prevent the handle release from

going in and prevent the handle from being moved.

Pusher Rod

Blocked

Connecting Rod

Pusher Rod

CR 194 One/Two-High Vacuum Limitamp

®

AR Control

Page 5