Cable entry from top or bottom, Dimensions – GE Industrial Solutions Limitamp AR User Manual

Page 16

Advertising
background image

CR 194 One/Two-High Vacuum Limitamp

®

AR Control

Page 16

Cable Entry From Top or Bottom

Removable cable entry plates are provided on the top and

bottom of the equipment.

Step 1: Remove cable entry cover plates. Cut an appropriate

size hole for required conduit bushing.

Step 2: Install a conduit bushing(s) capable of sealing against

20-psig minimum pressure on all cables entering or exiting the

arc resistant unit.

WARNING: Conduit bushings capable of sealing against

20-psig minimum should be installed on all cables

entering or exiting the enclosure. If these bushings are not

installed, hot arc gases can escape thru open area around

cables. Serious injury or death may result.

Figure 35. Conduit cover plate in plenum for top

cable entry.

Conduit Cutout Cover Plates

Plenum

Dimensions

Vacuum Limitamp AR controllers are normally 42-inches deep

and 90-inches high. The width of the CR 194 Two-High

Vacuum Limitamp AR is 36 inches (40 inches optional).

Refer Figure 38 (Bottom cable entry) and Figure 39 (Top cable

entry) for dimensional details.

The width of the 800A CR 194 One-High Vacuum Limitamp AR

is 48 inches. Refer to Figure 40.

Figure 37. Assembly of conduit bushing on the bottom

conduit plates for bottom cable entry.

Figure 36. Assembly of conduit bushing on to the

plenum top cover for top cable entry.

Conduit

Bushing

Conduit

Bushing