Installing the Current Sensors

The current sensors (CTs) must be installed
differently in the two breaker frame sizes.

LA-600, LA-800 and RL-800 Current Sensors
The following procedure is illustrated in Figure 15.
1. Slide two of the CTs over the outer load studs

with their terminals pointing upward. Slide the

other CT over the centerline stud with its

terminals pointing downward.

2. Connect the CT leads from the trip unit to each

CT. The leads are labeled with the letter of the

corresponding pole (A is the right pole from rear

of the breaker, B center, C left), and are also cut to

the appropriate lengths. Attach the white wire to

the terminal marked with a white paint dot on the

A and C (outer) CTs. Attach the black wire to the

terminal marked with a white paint dot on B

(center) CT. This difference is necessary to main-

tain polarity.

3. Reattach the primary disconnect assemblies to all

the studs if the breaker is unfused or to only the

load (lower) studs if the breaker is fused.

4. If the breaker is fused, reinstall the fuse assem-

blies on the upper studs.

LA-1600 Current Sensors
The following procedure is illustrated in Figure 16a.
1. Slide the three current sensors (CTs) over the

lower (load) studs, with the terminals pointing up.

2. Connect the CT leads from the trip unit to each of

the CTs. The leads are labeled with the letter of

the corresponding pole (A is the right pole from

rear of the breaker, B is the center pole, C is the

left pole), and are also cut to the appropriate

lengths. Attach the white wire to the terminal

marked with a white paint dot.

3. Reattach the primary disconnect assemblies to all

the studs if the breaker is unfused or to only the

load (lower) studs if the breaker is fused.

4. If the breaker is fused, reinstall the fuse assem-

blies on the upper studs.

RL-1600 Current Sensors
The following procedure is illustrated in Figure 16b.
1. Slide the three current sensors (CTs) over the

lower (load) studs, with the terminals pointing up.

Identify the left and right pole CTs based on the

location of the tie-wrap as shown in Figure 16b.

Left pole & right pole CTs should be shifted a little

towards center.

2. Connect the CT leads from the trip unit to each of

the CTs. The leads are labeled with the letter of

the corresponding pole (A is the right pole from

rear of the breaker, B is the center, C is the left),

and are also cut to the appropriate lengths. Attach

the white wire to the terminal marked with a

white paint dot.





3. Reattach the primary disconnect assemblies to all

the studs if the breaker is unfused or to only the

load (lower) studs if the breaker is fused.

4. If the breaker is fused, reinstall the fuse assem-

blies on the upper studs.

Figure 15. Installing the CTs on an LA-600 or LA-800 breaker

Figure 16a. Installing the CTs on an LA-1600 breaker.






CT Wire Exit

Hole

CT Wire Exit

Hole

Identify

Left Pole

Identify

Right Pole