SECTION 3. BREAKER PREPARATION

The following steps are performed to prepare the
breaker for installation of the new conversion kit.
Unless otherwise indicated, the procedure is the
same for LA-600, LA-800, LA-1600, RL-800, RL-1600,
and RL-2000 breakers.

WARNING:

Before installing the conversion kit, turn

the breaker OFF, disconnect it from all voltage
sources, and discharge the closing springs.

1. Open the breaker and remove it from its enclo-

sure. Carefully place the breaker on a suitable

work surface so that the rear of the breaker is

initially accessible.

2. If the conversion kit is to be installed on a fused

breaker (LAF series), remove the fuse structure

from the upper (line) studs to allow easier access

to the load studs.

3. Loosen the two Allen-head screws securing each

of the primary disconnects to the line (upper) and

load (lower) studs and remove the primary

disconnects, as illustrated in Figures 1 & 1a.

4. Remove the wires from the original current sen-

sors (CTs), if present, and slide off the CTs.

5. Unscrew the knob on the end of the manual

charging handle and pull the handle down part

way. Remove the two bolts holding the escutch-

eon to the breaker frame and lift off the

escutcheon.

6. Carefully position the breaker so that it is resting

on its back on the line and load studs.

7. Remove the two bolts securing the old flux shifter

mounting bracket (if present) to the breaker

frame. One bolt is secured with a nut, the other is

attached to a tapped hole in the frame.

Disconnect the two connectors on the leads to the

trip unit and remove the flux shifter.

8. Remove the three bolts securing the trip unit

mounting bracket (if present) to the breaker

frame. Remove the trip unit and its wiring har-

ness.

Notes:
Prior to installing the new flux shifter on the LA-

Gold breakers remove the old link [14] located as

shown in figure 2. After installing the new flux

shifter, assemble the link back.

Figure 1. Primary disconnects removed from the lower studs,

showing the original current sensors (LA-1600 shown)

Figure 1a. Primary disconnects removed from the lower studs,

showing the original current sensors (RL-2000 shown)

Figure 2. Original flux shifter and trip unit (Type LTS1 shown)

mounting locations (LA-1600 shown)

Breaker

Reset

Link

Trip

Paddle

Link [14]

Allen-head