SECTION 6. FOUR-WIRE GROUND
FAULT OPTION

The ground fault option for four-wire installations
requires the installation of an additional current
sensor on the neutral bus in the equipment. The
sensor is connected to the trip unit through the
connector provided in the wiring harness.
1. Mount the neutral sensor on the outgoing neutral

lead, normally in the bus or cable compartment in

the equipment. Figure 19 shows the sensor

outlines for the 600 A and 800 A frame sizes.

Figure 20 shows the sensor outlines for the 1600

A and 2000 A frame sizes.

2. Connect the neutral sensor wire harness to the

correct taps on the sensor. To maintain the same

polarity as the phase sensors, connect the white

wire to the common terminal, black to the tap.

3. Route the wires through the equipment and

connect to the two-pin connector on the trip unit

wiring harness, routed through the rear of the

breaker with the CT wires. The wires should be

tied to the breaker frame in an easily accessible

location.



Figure 19. Neutral sensor outline for 600A and 800A breakers

Figure 20. Neutral sensor outline for 1600A and 2000A breakers