Specifications environmental, Catalog numbers, Chapter 1 – introduction – GE Industrial Solutions POWER LEADER ModBus Monitor User Manual

Page 14: Power leader modbus monitor, Specifications, Environmental

Advertising
background image

POWER LEADER Modbus Monitor

Chapter 1 – Introduction

8

Specifications

The specifications of the Modbus Monitor are listed in
Table 2.

Parameter

Value

Control power

100–240 Vac, 50, 60 Hz;
125–250 Vdc;
30 W min

Current draw for fusing

Use 1.5A – 3.0A slow-blow fuse

Modbus communications

Two RS-485 ports, 1200 baud, 2400 baud, 4800
baud, 9600 baud, and 19.2 Kbaud supported; no
parity, eight data bits, one stop bit.
Mating connector: Precision Connector Designs
(PCD) ELFT03260 or equivalent (supplied with
unit)

RS-485 Modbus
interconnections

Bare wire, AWG #12–24

Standards:

UL 508, File No. E146421

CSA: C22.2 No. 14, File No. LR-77871-25

Device types supported

The Monitor supports up to 32 device types,
including the 21 Tightly Integrated Device types
and the Modbus Monitor device type itself.

Devices per Modbus
segment

Per the Modbus standard, up to 32 total ‘drops’
(devices) per segment, including Monitors and (if
applicable) PMCS host.
Up to 215 commnet devices may be supported via
Modbus Concentrators.
See GEH-6502, PMCS Network Architecture
Guide
, for details.

Compatible Modbus RTU
Host Software

GE Industrial Systems
Power Management Control System, version 5.1 or
greater

Table 2. Monitor specifications.

Environmental

The environmental requirements of the Monitor are
listed in Table 3.

Parameter

Value

Operating temperature

0° C to +65° C

Storage temperature

–20° C to +80° C

Relative humidity

5% to 95% noncondensing

Environmental exposure

NEMA 12

Vibration response and

endurance

IEC 255–21–1

Severity Class 1

Fast transient surge

ANSI C37.90.1

Radiated EMI withstand

ANSI C37.90.2

Electrostatic discharge

IEC 801–2

Severity Class 4

Table 3. Monitor environmental requirements.

Catalog Numbers

Two versions of the Monitor are available: a single RS-
485 port version and a dual RS-485 port version. Catalog
numbers for each version are shown in Table 4.

Description

Catalog Number

Monitor, single RS-485 port

PLMNTR1

Monitor, dual RS-485 port

PLMNTR2

Table 4. Monitor catalog numbers.