Chapter 2 – Installation

11

When the assembly is complete, plug the connector into
port labeled Segment A on the side of the Monitor, as
shown in Figure 10.





6KLHOG





,Q

2XW

,1

287

Figure 10. RS-485 port and RS-485 connector pinouts.

The connectors labeled

IN

should be wired to the cable

coming from the host (or previous device), or should be
terminated if the Monitor is the first device on the
Modbus segment. The

OUT

connectors are wired to the

RS-485 IN

connector of the next Modbus device, or

terminated if the Monitor is the final device on the
Modbus segment. Please study and follow the RS-485
grounding considerations and termination rules below to
ensure the correct operation of your Modbus segments.

If the Monitor is to be connected to a second Modbus
segment, follow the procedures outline above to wire the
connector, and plug it into the port labeled Modbus
Segment B on the side of the Monitor. Note that
termination considerations are independent for each
segment; i.e., the Monitor may need to be terminated for
one or both RS-485 segments, or for neither, if it is
positioned in the middle of the segment(s).

RS-485 Termination Considerations

Per the EIA485 standard, every RS-485 network must be
terminated at both ends. If the Modbus Monitor is the
first device, place the supplied 120-ohm, 1/2-watt
resistor between the + and - connectors of the

RS-485 IN

port. If the Modbus Monitor is the last device, place the
supplied 120-ohm, 1/2-watt resistor between the + and -
connectors of the

RS-485 OUT

port.

Figure 11 illustrates appropriate termination of an RS-
485 segment at the Modbus Monitor





6KLHOG





,Q

2XW

,1

287

7HUPLQDWLRQ ZKHQ

0RQLWRU LV ),567 GHYLFH

RQ 0RGEXV VHJPHQW

7HUPLQDWLRQ ZKHQ

0RQLWRU LV /$67 GHYLFH

RQ 0RGEXV VHJPHQW





6KLHOG





,Q

2XW

,1

287

Figure 11. RS-485 Terminations.