POWER LEADER Modbus Monitor

Appendix B – Modbus Monitor Register Map

53

Appendix B:

Modbus Monitor Register Map

This Appendix provides the Register Map of the Modbus
Monitor.

Only two sorts of Input Registers are supported:
Dynamic Value Registers and Event Registers.

Other registers such as R0, R1, R2, R3 are not being
supported.

Note the final column (Number of Registers) indicates
how many registers will be received when the indicated
register is requested. For example, when register R40340
is requested, two registers are returned.

Address

Contents

Units/Value/Range

Type

(R = Read only
RW = Read/Write)

Format

Number of
Registers

R40340

IEM Time Register

XX SS MM HH

RW

Long (BCD)

2

R40342

IEM Date Register

XX DD MM YY

RW

Long (BCD)

2

R41000

Product ID

30

R

unsigned integer

1

R41001

Modbus Address

R

unsigned integer

1

R41002-R41003

Serial Number

R

unsigned long integer
(First Register contains Low
Word, Second contains High
Word)

2

R41004-R41005

Firmware Revision

R

unsigned long integer
(First Register contains the
integer part, Second Register
contains the decimal part:
High Byte = 0.1*N
Low Byte = 0.01*M)

2

R41012

Proxy Status
Indicator

0h - if PMCS Modbus Monitor

Proxy software is not present

1h - if PMCS Modbus Monitor

Proxy software is present

RW

unsigned integer

1

R41013

Event Logger
Indicator

0h - if PMCS Event Logger client

software is not present

1h - if PMCS Event Logger client

software is present

RW

unsigned integer

1

R41014-R41023

Reserved

1

R41100-R41150

Reserved

1