Modbus Memory Map

NOTE: A multiplier factor may be necessary in cases where an integer value is returned but the Range and/or Step imply a
greater precision. In these cases, it is necessary to divide the returned value by 10 for a step of "0.1" or "0.5"; by 100 for a step of
".01"; and so on. Similarly, it is necessary to multiply by these factors prior to writing a settings value. This note does

not apply

to any step value greater than 1 (a step of "10" does not require a multiplier, for example). This note also does not apply to
values returned in floating point format. See the format codes at the end of the map for more information.

NOTE: Discrete I/O output state registers (Contact Output x State – register range from x9180 to x91FF and Contact Output
States – register range from xB256 to 0xB25D) contain correct information only when FlexLogic Active register (x0034) contains
value 1 (yes).

Addr

Register Name

Range Units Step Format Factory Default

Product Information (Read Only)

0000

Product Type

0 to 2

---

1

F716

0 (Low Voltage

Switchgear)

0001

Serial Number

---

---

---

F203

"0"

0009

External Ethernet MAC Address

---

---

---

F072

0

000C

Reserved (3 items)

---

---

---

F001

0

000F

CPU Hardware Version

0 to 655.35

---

0.01

F001

100

0010

CPU Firmware Version

0 to 655.35

---

0.01

F001

100

0011

CPU Firmware Boot Code Version

0 to 655.35

---

0.01

F001

100

0012

Build Date

---

---

---

F200

"0"

0026

Synchronizer Board Status

0 to 1

---

1

F102

0 (Disabled)

0027

Synchronizer Board Frequency Setting

50 to 60

Hz

10

F001

60

0028

Last Energy Clear Date

0 to 4294967295

---

1

F050

0

002A

Last CPU Commissioned Date

0 to 4294967295

---

1

F050

0

002C

Expected Node Protocol Version

0 to 655.35

---

0.01

F001

0

002D

Summary Number

---

---

---

F205

"0"

0033

Line Up

0 to 99

---

1

F001

1

0034

FlexLogic Active

0 to 1

---

1

F126

0 (No)

0035

Reserved (203 items)

---

---

---

F001

0

Installation (Read/Write Setting)

0100

CPU ID

0 to 1

---

1

F717

0 (CPU A)

0101

CPU Commissioned

0 to 1

---

1

F102

0 (Disabled)

0102

CPU Name

---

---

---

F200

"UNNAMED"

0116

System Frequency

50 to 60

Hz

10

F001

60

0117

Phase Rotation

0 to 1

---

1

F106

0 (ABC)

0118

Reserved (232 items)

---

---

---

F001

0

Clock (Read/Write Command)

0200

RTC Set Time

0 to 4294967295

---

1

F050

0

Clock (Read Only)

0202

Date Time Changed

0 to 4294967295

---

1

F050

0

0204

Reserved (8 items)

---

---

---

F001

0