F203

TEXT16

16 CHARACTER ASCII TEXT

F204

TEXT80

80 CHARACTER ASCII TEXT

F205

TEXT12

12 CHARACTER ASCII TEXT

F300

UINT16

FLEXLOGIC BASE TYPE (6 bit type)











The flexlogic BASE type is 6 bits and is combined with a 9 bit descriptor and 1 bit
for protection element to form a 16 bit value. The combined bits are of the form :
PTTTTTTDDDDDDDDD where P bit if set, indicates that the flexlogic type is
associated with a protection element state and T represents bits for the BASE
type, and D represents bits for the descriptor. The values in square brackets
indicate the base type with P prefix [PTTTTTT] and the values in round brackets
indicate the descriptor range.

[0] Off(0) this is boolean FALSE value

[0] On (1)This is boolean TRUE value

[2] CONTACT INPUTS (1 - 96)

[3] CONTACT INPUTS OFF (1-96)

[4] VIRTUAL INPUTS (1-64)

[6] VIRTUAL OUTPUTS (1-64)

[10] CONTACT OUTPUTS VOLTAGE DETECTED ( 1-64)

[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1-64)

[12] CONTACT OUTPUTS CURRENT DETECTED (1-64)

[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1-64)

[14] REMOTE INPUTS (1-32)

[28] INSERT (Via Keypad only)

[32] END

[34] NOT (1 INPUT)

[36] 2 INPUT XOR (0)

[38] LATCH SET/RESET (2 INPUTS)

[40] OR (2-16 INPUTS)

[42] AND (2-16 INPUTS)

[44] NOR (2-16 INPUTS)

[46] NAND (2-16 INPUTS)

[48] TIMER (1-32)

[50] ASSIGN VIRTUAL OUTPUT (1 - 64)

[52] SELF-TEST ERROR (See F141 for range)

[56] ACTIVE SETTING GROUP (1-8)

[62] MISCELLANEOUS EVENTS (See F146 for range)

[64-127] ELEMENT STATES (Refer to Memory Map Element States Section)

F500 UINT16

PACKED

BITFIELD











First register indicates I/O state with bits 0(MSB)-15(LSB) corresponding to I/0
state 1-16. Second register indicates I/O state with bits 0-15 corresponding to I/0
state 17-32 (if required). Third register indicates I/O state with bits 0-15
corresponding to I/0 state 33-48 (if required). Fourth register indicates I/O state
with bits 0-15 corresponding to I/0 state 49-64 (if required). The number of
registers required is determined by the specific data item.
A bit value of 0 = Off, 1 = On

F701

BITFIELD

SRCx Node Internal Diagnostics Bit Mask

0

Power-on Self Test Error Detected

1

Built-In-Test Error Detected

2

Invalid Data Detected

3

Jamb sync occurred over threshold

4

Invalid node configuration detected

5

Invalid CRC check of node firmware