GE Industrial Solutions Entellisys Integrator’s Guide User Manual

Page 35

Advertising
background image

35

5CB0

SRC x OV Trip Time Delay

0.5 to 600

---

0.5

F001

300

5CB1

SRC x OV Trip Phase Requirement

1 to 3

---

1

F001

1

5CB2

SRC x OV Trip Open or Trip Setting

0 to 1

---

1

F727

1 (Trip and activate

lockout)

5CB3

SRC x OV Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

5CB4

SRC x OV Alarm Pickup Threshold

105 to 125

---

1

F001

120

5CB5

SRC x OV Alarm Time Delay

0.5 to 600

---

0.5

F001

150

5CB6

SRC x OV Alarm Phase Requirement

1 to 3

---

1

F001

1

5CB9

Reserved2 (7 items)

0 to 65535

---

1

F001

0

5CBE

SRC x PL Trip Enable

0 to 1

---

1

F102

0 (Disabled)

5CBF

SRC x PL Trip Pickup Setting

8 to 50

---

1

F001

8

5CC0

SRC x PL Trip Time Delay

0.5 to 600

---

0.5

F001

300

5CC1

SRC x PL Trip Block Volt Enable

0 to 1

---

1

F102

0 (Disabled)

5CC2

SRC x PL Open or Trip Setting

0 to 1

---

1

F727

1 (Trip and activate

lockout)

5CC3

SRC x PL Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

5CC4

SRC x PL Alarm Pickup Setting

8 to 50

---

1

F001

8

5CC5

SRC x PL Alarm Time Delay

0.5 to 600

---

0.5

F001

150

5CC6

SRC x PL Alarm Block Volt Enable

0 to 1

---

1

F102

0 (Disabled)

Source Settings (Read Only) (30 modules)

5CC7

SRC x PL Trip Voltage Setting

5 to 5

---

1

F001

5

5CC8

SRC x PL Alarm Blocking Voltage Setting

5 to 5

---

1

F001

5

Source Settings (Read/Write Setting) (30 modules)

5CC9

Reserved3 (3 items)

0 to 65535

---

1

F001

0

5CCC

SRC x Rev Power Trip Enable

0 to 1

---

1

F102

0 (Disabled)

5CCD

SRC x Rev Power Trip Pickup Setting

10 to 990

---

10

F001

990

5CCE

SRC x Rev Power Trip Time Delay

0.5 to 600

---

0.5

F001

300

5CCF

SRC x Rev Power Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

5CD0

SRC x Rev Power Alarm Pickup Setting

10 to 990

---

10

F001

990

5CD1

SRC x Rev Power Alarm Time Delay

0.5 to 600

---

0.5

F001

150

5CD2

SRC x Rev Power Trip or Open

0 to 1

---

1

F727

1 (Trip and activate

lockout)

5CD3

Reserved4 (4 items)

0 to 65535

---

1

F001

0

5CD7

SRC x High Curr Alarm Enable

0 to 1

---

1

F102

0 (Disabled)

5CD8

SRC x High Curr Alarm Pickup Setting

50 to 200

---

5

F001

200

5CD9

SRC x High Curr Alarm Time Delay

1 to 15

---

1

F001

15

5CDA

Reserved5 (5 items)

0 to 65535

---

1

F001

0

5CDF

SRC x Total Breaker Operations

0 to 65535

---

1

F001

0

5CE0

SRC x Total Breaker No Load Operations

0 to 65535

---

1

F001

0

5CE1

SRC x Total Breaker Load Operations

0 to 65535

---

1

F001

0

5CE2

SRC x Total Breaker Fault Operations

0 to 65535

---

1

F001

0

5CE3

SRC x Breaker Percent Load Life

0 to 655.35

---

0.01

F001

0

Source Settings (Read Only) (30 modules)

5CE4

SRC x Percent Mechanical Life

0 to 655.35

---

0.01

F001

0

Source Settings (Read/Write Setting) (30 modules)

5CE5

SRC x Time Date Last Breaker Operation

0 to 4294967295

---

1

F050

0

Advertising