GE Industrial Solutions Entellisys Integrator’s Guide User Manual
Page 60
60
8
Start Firmware Download
9
Switch Firmware
10
Cancel Firmware Download
11
Ignore CPU Message
12
Firmware Packet Present
13
Flux Shifter Open
14
Flux Shifter Trip
15
Not Used
F708
BITFIELD
SRCx Node Physical Status
0
Breaker Contacts Open
1
Breaker Contacts Closed
2
Lockout
3
Closing Spring Charged
4
Primary Connected
5
Primary Disconnected
6
Secondary Connected
7
Door Interlock
8
Analog IOC
9
Not Used
10
Not Used
11
Not Used
12
Not Used
13
Not Used
14
Not Used
15
Not Used
F709
BITFIELD
SRCx Node Logic and Trip Status
0
Synchronization Source Bit 0
1
Synchronization Source Bit 1
2
Download Source Bit 0
3
Download Source Bit 1
4
Download Complete
5
Test Mode
6
GF Suspend
7
Not Used
8
Trip Flag
9
Trip due to LT
10
Trip due to ST
11
Trip due to GF
12
Trip due to IOC
13
Phase Indicator Bit 0
14
Phase Indicator Bit 1
15
Not Used
F711
ENUMERATION
SRCx Long Time Delay Band Setting
0
BAND 1
1
BAND 2
2
BAND 3
3
BAND 4
F712
ENUMERATION
SRCx Breaker Connection
0
Forward
1
Reverse
F713 ENUMERATION
Delay
Band
Settings
0
BAND 1