GE Industrial Solutions Entellisys Integrator’s Guide User Manual

Page 60

Advertising
background image

60

8

Start Firmware Download

9

Switch Firmware

10

Cancel Firmware Download

11

Ignore CPU Message

12

Firmware Packet Present

13

Flux Shifter Open

14

Flux Shifter Trip

15

Not Used

F708

BITFIELD

SRCx Node Physical Status

0

Breaker Contacts Open

1

Breaker Contacts Closed

2

Lockout

3

Closing Spring Charged

4

Primary Connected

5

Primary Disconnected

6

Secondary Connected

7

Door Interlock

8

Analog IOC

9

Not Used

10

Not Used

11

Not Used

12

Not Used

13

Not Used

14

Not Used

15

Not Used

F709

BITFIELD

SRCx Node Logic and Trip Status

0

Synchronization Source Bit 0

1

Synchronization Source Bit 1

2

Download Source Bit 0

3

Download Source Bit 1

4

Download Complete

5

Test Mode

6

GF Suspend

7

Not Used

8

Trip Flag

9

Trip due to LT

10

Trip due to ST

11

Trip due to GF

12

Trip due to IOC

13

Phase Indicator Bit 0

14

Phase Indicator Bit 1

15

Not Used

F711

ENUMERATION

SRCx Long Time Delay Band Setting

0

BAND 1

1

BAND 2

2

BAND 3

3

BAND 4

F712

ENUMERATION

SRCx Breaker Connection

0

Forward

1

Reverse

F713 ENUMERATION

Delay

Band

Settings

0

BAND 1