GE Industrial Solutions Entellisys Integrator’s Guide User Manual
Page 34
34
5768
...Repeated for module number 25
57B7
...Repeated for module number 26
5806
...Repeated for module number 27
5855
...Repeated for module number 28
58A4
...Repeated for module number 29
58F3
...Repeated for module number 30
Source Settings (Read/Write Setting) (30 modules)
5C8A
SRC x Node Commissioned
0 to 1
---
1
F102
0 (Disabled)
Source Settings (Read Only) (30 modules)
5C8B
SRC x PT Source Node Identifier
0 to 29
---
1
F001
0
Source Settings (Read/Write Setting) (30 modules)
5C8C
SRC x Breaker Connection
0 to 1
---
1
F712
0 (Forward)
5C8D
SRC x IOC Enabled
0 to 1
---
1
F718
1 (Enabled)
5C8E
SRC x IOC Pickup Setting Multiplier
1.5 to 15
---
0.5
F001
60
5C8F
SRC x Ground Fault Protection Switch
0 to 1
---
1
F102
0 (Disabled)
5C90
SRC x Short Time Protection Switch
0 to 1
---
1
F102
1 (Enabled)
5C91
SRC x Short Time Pickup Setting
1.5 to 9
---
0.5
F001
50
5C92
SRC x Short Time I2T Curve
0 to 1
---
1
F102
0 (Disabled)
5C93
SRC x Short Time Delay Band Setting
0 to 6
---
1
F713
2 (BAND 3)
5C94
SRC x Long Time Delay Band Setting
0 to 3
---
1
F711
1 (BAND 2)
5C95
SRC x Ground Fault Protection Alarm Select
0 to 1
---
1
F714
0 (Trip)
5C96
SRC x Ground Fault Protection I2T Curve
0 to 1
---
1
F102
1 (Enabled)
5C97
SRC x Ground Fault Protection Pickup Setting
0.2 to 0.6
---
0.01
F001
24
5C98
SRC x Ground Fault Protection Delay Band
Setting
0 to 6
---
1
F713
2 (BAND 3)
5C99
SRC x PT Rating
0 to 6
---
1
F719
0 (None)
5C9A
SRC x UV Trip Enable
0 to 1
---
1
F102
0 (Disabled)
5C9B
SRC x UV Trip Curve Type
0 to 1
---
1
F726
1 (Constant time curve)
5C9C
SRC x UV Trip Pickup Setting
50 to 95
---
1
F001
50
5C9D
SRC x UV Trip Time Delay
0.5 to 600
---
0.5
F001
300
5C9E
SRC x UV Trip Phase Requirement
1 to 3
---
1
F001
1
5C9F
SRC x UV Block Voltage Enable
0 to 1
---
1
F102
0 (Disabled)
5CA0
SRC x UV Trip Block Volt Setting
5 to 75
---
1
F001
5
5CA1
SRC x UV Trip Open or Trip Setting
0 to 1
---
1
F727
1 (Trip and activate
lockout)
5CA2
SRC x UV Alarm Enable
0 to 1
---
1
F102
0 (Disabled)
5CA3
SRC x UV Alarm Curve Type
0 to 1
---
1
F726
1 (Constant time curve)
5CA4
SRC x UV Alarm Pickup Setting
50 to 95
---
1
F001
50
5CA5
SRC x UV Alarm Time Delay
0.5 to 600
---
0.5
F001
150
5CA6
SRC x UV Alarm Phase Requirement
1 to 3
---
1
F001
1
5CA7
SRC x UV Alarm Block Volt Enable
0 to 1
---
1
F102
0 (Disabled)
5CA8
SRC x UV Alarm Block Volt Setting
5 to 75
---
1
F001
5
5CA9
Reserved1 (5 items)
0 to 65535
---
1
F001
0
5CAE
SRC x OV Trip Enable
0 to 1
---
1
F102
0 (Disabled)
5CAF
SRC x OV Trip Pickup Setting
105 to 125
---
1
F001
120