59

7

Not

Used

8

Not

Used

9

Control_Power1_Status

10

Control_Power2_Status

11

App Flash CRC Fail

12

Boot Flash CRC Fail

13

Option Box Failure

14

Not

Used

15

Not

Used

F705

BITFIELD

SRCx NodeProt Protection Function Configuration

0

Ground Fault Protection Enabled

1

Instantaneous Overcurrent Protection Enabled

2

Short Time Protection Enabled

3

Switchable ST/IOC Protection Enabled/Disabled

4

Switchable GF

5

Not Used

6

Not Used

7

Not Used

8

Not Used

9

Not Used

10

Not Used

11

Not Used

12

Not Used

13

Not Used

14

Not Used

15

Not Used

F706

BITFIELD

SRCx Reflected CPU Diagnostics

0

CPU A is using the hardware clock

1

CPU A is not receiving data from one or more nodes

2

CPU A Identifier

3

CPU A Running Flex Logic

4

CPU B Running Flex Logic

5

Not Used

6

Not Used

7

Not Used

8

CPU B is using the hardware clock

9

CPU B is not receiving data from one or more nodes

10

CPU B Identifier

11

CPU A Running Flex Logic

12

CPU B Running Flex Logic

13

Not Used

14

Not Used

15

Not Used

F707

BITFIELD

SRCx Reflected CPU Commands

0

No Op

1

Open

2

Close

3

Trip

4

Network Interlock

5

Reset Interlock

6

Light LED

7

ATO Mode