Modbus Memory Map Format Codes

Format Name Format Type/Bitmask Format Definition

F001

UINT16

UNSIGNED 16 BIT INTEGER

F003

UINT32

UNSIGNED 32 BIT INTEGER (2 registers)

High order word is stored in the first register.

Low order word is stored in the second register.

F013

POWER_FACTOR

POWER FACTOR (SIGNED 16 BIT INTEGER)

Positive values indicate lagging power factor; negative values indicate leading.

F050

UINT32

TIME and DATE (UNSIGNED 32 BIT INTEGER)

Gives the current time in seconds elapsed since 00:00:00 January 1, 1970.

F060

FLOATING_POINT

IEEE FLOATING POINT (32 bits)

F072

HEX6

6 BYTES - 12 ASCII DIGITS

F102 ENUMERATION

DISABLED/ENABLED

0

Disabled

1

Enabled

F106 ENUMERATION

PHASE

ROTATION

0

ABC

1

ACB

F108 ENUMERATION

OFF/ON

0

Off

1

On

F118

ENUMERATION

WAVEFORM CAPTURE MODE

0

Automatic Overwrite

1

Protected

F126 ENUMERATION

NO/YES

CHOICE

0

No

1

Yes

F127

ENUMERATION

LATCHED OR SELF-RESETTING

0

Latched

1

Self-Reset

F131

ENUMERATION

FORCED CONTACT OUTPUT STATE

0

Disabled

1

Energized

2

De-energized

3

Freeze

F144

ENUMERATION

FORCED CONTACT INPUT STATE

0

Disabled

1

Open

2

Closed

F176

ENUMERATION

SYNCHROCHECK DEAD SOURCE SELECT

0

None

1

LV1 and DV2

2

DV1 and LV2

3

DV1 or DV2

4

DV1 xor DV2

5

DV1 and DV2

F200

TEXT40

40 CHARACTER ASCII TEXT

20 registers -16 Bits: 1st Char MSB, 2nd Char. LSB