CH. 5: PLC CONFIG 23 SEP 1999 PAGE 33

e. Reference Addresses

In addition to the length of each of the four I/O references (%I, %Q, %AI, %AQ), the starting reference
address for each I/O type must be set for each of the I/O references with a non-zero length. This
reference address must not conflict with any other I/O module or Genius device.

f. Redundancy

If the AV-300i is used in a redundant application, this parameter should be set to YES.

g. Input Default

The input defaults can be set to OFF or HOLD, as desired.

h. Outputs Enabled

If outputs from the PLC are to be enabled (most cases), this parameter should be set to YES.

NOTE: The reference types available for mapping into Series 90-30 memory are more numerous than

those available for the Series 90-70. This is due to the fact that the Series 90-70 performs more data
type checking than the Series 90-30. This extra checking requires that the number and type of memory
references match exactly in the Series 90-70. The Series 90-30 requires only that the amount of
data match exactly.

5.3

Series 90-30 Configuration

For full information on the configuration of Genius LANs with the Series 90-30 PLC, consult the GE
Fanuc’s

Series 90-30 Genius Bus Controller User's Manual

.

The Series 90-30 PLC is configured using Logicmaster 90-30. In the configuration package, the Genius
Bus Controller (GBC) configuration screen appears as follows: