background image

PAGE 40 23 SEP 1999 CH.7: WIRING

7.2

RS232/RS485 Pinout:

The following jumpers are associated with RS485 (J2).

a.

JP1 - Jumper on places a 120 Ohm terminating resistor on the circuit.

b.

JP2 - Places 5 volts at J2, Pin 9. JP2 consists of six individuals headers. All headers must be

placed on the right side of JP2 for RS-232 operation or placed on the left side for RS-485.

c.

JP3 – Must be jumpered for RS-232 operation and must be removed for RS-485 operation.

d.

JP4 – Do NOT jumper.

For more information on the hardware setup, see the GE Control Toolbox Help file.

1 2 3 4

5

6 7 8 9

RECEPTACLE ASSEMBLY

CONTACT NUMBERS

RS-232 APPLICATION

1
2
3
4
5
6
7
8
9

CD OUT*
TXD OUT
RXD IN
NO CONNECTION
GND
DSR OUT*
CTS IN
RTS OUT
RI OUT*

CONNECTED TO PIN 4

DO NOT CONNECT

100 OHM PULL DOWN

DO NOT CONNECT

RS-485 APPLICATION

GND

5

9

8

7

6

+5 VOLTS

B

4

3

2

1

A

SHIELD

CONTACT DESCRIPTION

CONTACT DESCRIPTION

* CONTACTS 1, 6, AND 9 ARE
INTERNALLY CONNECTED IN
RS-232 MODE.

Advertising