2 metering, Metering – GE Industrial Solutions SG Series 225 & 300 Operating Manual User Manual

Page 25

Advertising
background image

Modifications reserved

Page 25/79

OPM_SGS_USM_M22_M30_2US_V010.doc

User Manual SG Series 225 & 300 UL S2

6.2 METERING

The METERING mode is entered any time the “METER” button is pressed.
The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like
AC, DC and various statistics.

In this mode the buttons perform the following functions:

Return to HOME screen.

Scrolls backward to the previous screen.

Scrolls forward to the next screen.

It is possible to view any pushbutton functional description by pushing the button for more than 3
seconds.

`

Home\Meter

BATTERY

V 545

V

I 50.0

A

T +25°

C

Charge level

80 %

Autonomy 10

Min

Battery data screen

V

The battery voltage.

I

The battery current (negative values correspond to
the discharge of the battery).

T

The temperature of the battery (“SENSOR DISABLE”
indicates sensor disabled).

Charge level

The battery charge level.

Autonomy

The estimated backup time with the
present load.


`

Home\Meter

RECTIFIER

f : 60.0 Hz

L12 :

480 V

Vdc

:

540 V

L23 :

480 V

Idc1

: 250.0 A

L31 :

480 V

Idc2

: 250.0 A


Rectifier utility data screen

f

The input frequency of the rectifier.

L12

L23

The voltage levels between the three phases (line-

L31 to-line).

Vdc

Rectifier voltage output.

Idc1

Output current 1

st

Rectifier bridge.

Idc2

Output current 2

nd

Rectifier bridge.


`

Home\Meter

UTILITY

f 60

Hz

L1 275

V

L2 279

V

L3 276

V

BYPASS FREE

Bypass utility data screen

f

The frequency of the utility.

L1

L2

Three-phase utility voltage PHASE /NEUTRAL.

L3

Bypass Bypass status: FREE / LOCKED.


Advertising