Installation Guide LP 33 Series 10-20 kVA

3.3.2

Storage of the battery


In case of extended storage, when the delivery includes maintenance free batteries, keep in mind that

they are subject to auto-discharging process

To avoid permanent damages to the battery, you must observe the following instructions:

The storage time without charging the battery depends on the temperature of the storage ambient.

The optimal ambient temperature for the batteries is 68°F (20°C).

For storage temperature higher than 68°F (20°C), the storage time will decrease.

Each additional 18°F (10°C) over the nominal temperature of 68°F (20°C) will decrease the storage

time, without freshening charge, by half.



In case of a maintenance free battery, the storage time without charging the battery is

approximately:

6 months with storage temperature 68°F (20°C)

3 months with storage temperature 86°F (30°C)

2 months with storage temperature 95°F (35°C)


NOTE !

In case of battery storage pay

attention to:

FRAGILE

SENSITIVE

TO DAMPNESS

TO HEAT

SENSITIVE

TO FROST