3.5 VENTILATION

AND

COOLING

The heat produced by the UPS is transferred to the environment by its internal blowers.

Airflow through the UPS
It is important that the cooling air can freely flow

through the air inlets and outlets of the UPS.

Fig. 4.5-1 Airflow through the LP 33 Series

NOTE !

Do not put any object on the top of the
cabinet: it might obstruct the air flow.

Heat evacuation from UPS room
The heat must be evacuated from the
environment with a proper cooling /
ventilation system provided by the

user.

Fig. 4.5-2 Heat evacuation from UPS room



Air volume and losses of the UPS
The approximate minimum air volume needed to evacuate the heat generated by the UPS, for inlet
temperature max. 35°C
(95°F), for the standard version at inverter nominal load with PF = 0.8 lag. and
battery charged, are the following:

Losses

Cooling air flow

UPS model

VFI Mode

ECO Mode

VFI Mode

ECO Mode

LP 33 Series / 30 kVA

8,874 BTU/hr

2.60 kW

1,673 BTU/hr

0.49 kW

448

CFM

760 m

3

/h

86

CFM

145 m

3

/h

LP 33 Series / 40 kVA

11,946 BTU/hr

3.50 kW

2,253 BTU/hr

0.66 kW

601

CFM

1,020 m

3

/h

115

CFM

195 m

3

/h