OPM_LPS_3UI_30K_40K_0US_V010.doc

Installation Guide LP 33 Series 10-20 kVA

3.9.3 Battery

connection


Before proceeding to an external battery connection, follow the Safety rules concerning the battery.

Make sure that the UPS is not powered and remove the external battery protections.

NOTE !

To meet standards concerning electromagnetic compliance, the connection between
the UPS and external Battery
must be done by using a shielded cable or suitable
shielded (metal) conduit!

List of possible battery configurations on LP 33 Series

Autonomy (min.)

Battery cabinet

Battery type

Block

number 30 kVA 40 kVA

Note

Standard cabinet battery

33 Ah – 12 V

24

10

8

See Fig. 3.9.3-1

Standard cabinet battery

33 Ah – 12 V

48

29

19

See Fig. 3.9.3-1

Standard cabinet battery

50 Ah – 12 V

24

19

12

See Fig. 3.9.3-1

Standard cabinet battery +
Additional cabinet 16.93” / 430mm

33 Ah – 12 V

96

(48+48)

65

44

See Fig. 3.9.3-2

Standard cabinet battery +
Additional cabinet 16.93” / 430mm

50 Ah – 12 V

48

(24+24)

45

33

See Fig. 3.9.3-2

UPS with standard cabinet battery

X4 Battery - Battery connection

-

= Negative pole of the battery

0 = Central point of battery blocks

+ = Positive pole of the battery

PE = Battery cabinet ground

Battery

-

0

+

PE

LPS33U_

030-040_

Connectio

n battery

_01US

X4

23.63"

40.55"

16.93"

600mm

1030mm

430mm

LP 33 Series

Standard

battery

cabinet

LPS33U_030-040_UPS+Cabinet battery_01

LP

S33U_

030-

040_Ba

tter

y c

onnec

tion_Di

agram_0

1

LP 33 Series

Standard

battery

cabinet

F5

F6

F7

0

-

+

-

0 +

X4 - Battery

-

0

+

-

0

+

F7

F6 F5

X4 - Battery

Fig. 3.9.3-1 Diagram battery connection

Note !

The UPS unit is supplied with the battery connected as above showed on Fig. 3.9.3-1.