Installation Guide LP 33 Series 10-20 kVA

How to access the terminals for the cable connections

LPS33U_

030-040_

Connecti

on_01US

OFF

ON

OFF

ON

Bottom entry cables

C

B

A

C

Fig. 3.8.1-1 Access to the input / output connections

To access input, output and battery connections
proceed as follows:

• Open the front door “A” of the cabinet.

• Remove the protection panel “B”.

• Remove the plate “C” for bottom cable entry.

NOTE !

Drill in the plate “C” appropriate holes for cable conduits (max. 4 x 2”).

See Fig 3.8.1-1 for details “C”.


3.8.2 Internal

fuse

ratings

LP 33 Series internal fuses

The UPS is equipped with battery

fuses F5, F6, F7.

In case of replacement the same
type and the same rating must be

used (see table below).

LPS33U_030-040

_F5-F6-F7_01

OFF

ON

OFF

ON

F7

F5

F6

Fig. 3.8.2-1 Battery fuses F5 – F6 – F7

WARNING !

The replacement of
battery fuses must

be performed by
QUALIFIED SERVICE
PERSONNEL only.

UPS

Battery fuses F5 – F6 – F7

LP 33 Series / 30 kVA

Fuse NH00 125A UL recognized

LP 33 Series / 40 kVA

Fuse NH00 160A UL recognized