Installation Guide LP 33 Series 10-20 kVA

EPO (Emergency Power Off)

An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on

terminals X2 / 1, 2 or connector J2 / 12, 25 of the Customer Interface (see Fig. 4.4-1 / X2 & J2).

7

89

1

0

11

22

21

20

19

18
7

J2

X1

2
1

JP3
X2

Fig. 4.4-2 PCB Customer Interface

LPS33U_030-040

_UPS+X7+JP5

1

2

X7

P1 - Control board

JP5

OFF

ON

OFF

ON

Fig. 4.4-3 PCB P1 – Control board

NOTE !

To enable this function, remove jumper JP3 on the Customer Interface and the
cable on the terminal X2 / 1, 2
(see Fig. 4.4-2).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP5 on the P1 – Control
board
are OFF (see Fig. 4.4-3).

In a parallel system a separate NC (Normally Closed) contact must be connected
individually to each unit
.

When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.

NOTE !

This procedure could imply a load shutdown.

When the EPO has been activated, the system must be restored as following:

Press the push-button EPO (contact on X2 / 1, 2 is closed again).

Perform the command INVERTER OFF entering the screen:
MENU/COMMAND MENU/INVERTER OFF.

COMMAND MENU

INVERTER ON

INVERTER OFF *

Start the inverter entering the screen:

MENU/COMMAND MENU/INVERTER ON.

COMMAND MENU

INVERTER ON *

INVERTER OFF