5 OPERATION & MAINTENANCE

! WARNINGS
Lead-acid batteries contain hazardous materials. Batteries must be handled, transported and recycled in

accordance with federal, state and local regulations. Because lead is a toxic substance, lead-acid batteries

must be recycled rather than discarded.

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the

required precautions. Keep unauthorized personnel away from batteries.

When replacing batteries, use the same number and type of batteries.

DC fuses operate at the rated battery voltage at all times. A blown DC bus fuse indicates a serious problem.

Serious injury or damage to the equipment can result if the fuse is replaced without knowing why it failed.

Do not open or mutilate the batteries.

Do not dispose of battery or batteries in a fire. The battery may explode.

A battery can present a risk of electrical shock and high short circuit current. The following precautions should

be observed when working on batteries:

Remove watches, rings and other metal objects.

Use tools with insulated handles.

Wear rubber gloves and boots.

Do not lay tools or metal parts on top of batteries.

Disconnect charging source prior to connecting or disconnecting battery terminals.

Determine if battery is inadvertently grounded. If inadvertently grounded, remove source of ground.

Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock

will be reduced if such grounds are removed during installation and maintenance.

Lead-acid batteries can present a risk of fire because they generate hydrogen gas. In addition, the electrical

connections must be protected against accidental short circuits, which can cause sparks. The following

procedures should be followed:

DO NOT SMOKE when near batteries.

DO NOT cause flame or spark in battery area.

Discharge static electricity from body before touching batteries by first touching a grounded metal

surface.

After replacing battery jars in a battery cabinet, replace the retaining straps that hold the jars in place

on the shelves. This will limit accidental movement of the jars and connectors should the cabinet ever

need to be repositioned or relocated.

Regular maintenance of the battery module is an absolute necessity. Periodic inspections of battery and

terminal voltages, specific gravity and connection resistance should be made. Strictly follow the procedures

outlined in the battery manufacturer’s manual, available on the manufacturer’s Web site.

Valve-regulated lead-acid (sealed-cell) batteries do require periodic maintenance. Although maintenance of

electrolyte levels is not required, visual inspections and checks of battery voltage and connection resistance

should be made.

NOTE
Do not use cleaners on the batteries. Solvents can make the battery cases brittle. Use only a dry cloth or a cloth

moistened in water.