Installation and O&M manual for SG battery cabinets - OPM_SGS_XXU_ISG_BAT_XUS_V020.doc
Installation Guide SG Series UL Battery cabinets
Startup Contact INFORMATION:
Date: ____________ Requested start up date: ____/____/____ Time: ______________
GE Zenith Sales Rep:________________________ Phone Number:___________________
Company name: ___________________________________________________________
Site Contact:_______________________________________________________________
Telephone #_______________Fax #_______________ E-mail_______________________
Facility/ End User Information:
Name ________________________________________________
Address
________________________________________________
City, State, Zip ___________________________________________
Contact ________________________________________________
Phone _____________ E-mail ____________________________
EQUIPMENT INFORMATION:
UPS Model #:
____________________________________
UPS Serial #:
____________________________________
INSTALLATION INFORMATION:
UPS / Battery
1. For 400/500 kVA UPS Only. Facing the back of the UPS, there are shipping restraints (yellow shipping
brackets and bolts) connected to the top inductor on the left side of the UPS. This bracket and
hardware must be removed prior to placing the UPS in its final installation location. Yes__ No__ N/A__
2. All packing materials are removed from UPS and battery cabinet and each is placed in its final installed
position. ---------------------------------------------------------------------------------------Yes__ No__ N/A__
3. Adequate workspace and clearances are provided around UPS and battery cabinet per NEC code and
the UPS installation manual.-----------------------------------------------------------------Yes__ No__ N/A__
4. The area around the UPS is clean (dust free) and free of conductive particles or moisture. Airborne
conductive particles can cause malfunctions of the UPS and possible damage to the UPS and its
connected loads. -----------------------------------------------------------------------------Yes__ No__ N/A__
5. Air conditioning is installed and operating properly. It should be sized for the maximum heat rejection
from the UPS at full load operation and recharging batteries. If the UPS will operate for a long period
during a power outage, then the hot air must be exhausted from the UPS room. The exhaust fan
should be powered by UPS output power. Otherwise, the UPS and battery will overheat and shut off
prematurely and possibly damage the UPS or battery. ----------------------------------Yes__ No__ N/A__
6. UPS internal input and output switches are open until the UPS is started (commissioned) by authorized
personnel. (The exception is the internal bypass switch may be closed if load power must be
established before commissioning. Input phase rotation [must be ABC Clockwise] should be checked
prior to closing the internal bypass switch.)------------------------------------------------Yes__ No__ N/A__