Installation and O&M manual for SG battery cabinets - OPM_SGS_XXU_ISG_BAT_XUS_V020.doc

Installation Guide SG Series UL Battery cabinets

5.4 BATTERY

OPERATION

The separate battery manufacturer’s manual, available on the battery manufacturer’s Web site, provides the

necessary information for the installation, operation, charging and maintenance of the battery. Use the battery

manual in conjunction with this manual.

For models with nominal 240-cell battery, the DC bus nominal float voltage range is 527 to 576 VDC. For

maximum equalize voltage see battery manufacturer data sheet. Battery voltage at end of discharge is 400.8

VDC at the battery.

Every 8°C (15°F) increase in temperature reduces the battery life by 50%. Once the battery is damaged by heat

its capacity cannot be improved.

Every 8°C (15°F) decrease in temperature reduces the battery life by 50%.

5.5 PROTECTION

EQUIPMENT CONNECTIONS

10-300kVA

Each battery system is supplied with a circuit breaker in the master cabinet and fuses in the secondary battery

cabinets.

400-750kVA

Each battery cabinet is supplied with a circuit breaker.

The transition cabinet, for the 750KVA, is supplied with 2-2000A rated semiconductor protection fuses. These

fuses are bolted to the landing plates with 3/8-16 Grade-8 hardware. The torque value for the hardware is 40-

44 ft. lbs.

UPS Cabinet KVA

Fuse/Circuit Breaker (CB)

Fuse Size CB Size

CB Torque Value

SG

27"

10 1 Fuse mod in each cab + 1 CB mod in Master

35 30

SG

27"

20 1 Fuse mod in each cab + 1 CB mod in Master

60 60

SG

27"

30 1 Fuse mod in each cab + 1 CB mod in Master

80 80

SG

27"

40 1 Fuse mod in each cab + 1 CB mod in Master

100 100

SG

27"

50 1 Fuse mod in each cab + 1 CB mod in Master

125 125

SG

27"

80 1 Fuse mod in each cab + 1 CB mod in Master

200 200

SG

27"

100 1 Fuse mod in each cab + 1 CB mod in Master

250 250

SG

27"

120 1 Fuse mod in each cab + 1 CB mod in Master

300 300

SG

27"

150 1 Fuse mod in each cab + 1 CB mod in Master

400 400

SG

27"

225

1 Fuse mod + 1 CB mod in each cab

300

300

SG

27"

300

1 Fuse mod + 1 CB mod in each cab

400

400

See circuit breaker

for the value