Secondary DC Power Distribution Bay H569-445

Issue 3 June 2012

27

Alarm Connections and ABS Power

At the top of the cabinet is a Customer Interface Board for connecting Output Alarms

and Alarm Battery Supply (ABS) to redundantly power the alarms and the VIM1C meter.

The VIM1C receives redundant power from panels 1 and 2 as well as an external ABS

connection, so the ABS connection is not mandatory for proper operation but some

customers require its use. A Return connection is required for operation of the meter

and alarms. The Return connection on the Customer Interface Board is factory wired

when internal return buses are ordered, otherwise it must be field wired to the external

return bus. Alarm Outputs consist of one form-C contact for power loss, one form-C for

current overload and one form-C contact for fuse/breaker alarms (Note: there are two

connection points for FAJ/CB but they are connected to the same form-C contact).

Contacts are rated for 60V, 1/2A. Maximum wire size to the terminal blocks is 12 gage.