Specifications

Output Voltage: -48Volts DC
Output Capacity: 800A per Distribution Panel

6 Load BDFB: 2400A per Side, 4800A Maximum per Bay

4 Load BDFB: 1600A per Side, 3200A Maximum per Bay

2 Load BDFB: 800A per Side, 1600A Maximum per Bay

Agency Approval: UL Listed (cULus), NEBs
Environment: 0C to +40C (+32F to +104F)
Cabinet:

Seismic Zone 4 Box Framework

Color: Central Office Soft Blue

Width: 26 inches (660mm) or 34 inches (864mm)

Height: 84 inches (2134mm)

Depth: 15 inches (381mm)

Weight: Approx. 375 pounds (6 panels)

Access: Front Fuse/Breaker and Alarm Access, Rear Wiring Access
Distribution: 28-Position Panel for Bullet-Style Protectors
Protectors:

• Bullet-Style Fuse Holders, TPS or TLS Fuses through 125A

• Single Pole LEL Bullet-Style Circuit Breakers through 100A

• Two-Pole LEL Bullet-Style Circuit Breakers through 150A

• Three-Pole LEL Bullet-Style Circuit Breakers through 250A

• No Protector Spacing Restrictions

• Maximum Loading

• 64% of protector rating - Continuous (List 1)

• 80% of protector rating - Maximum Load (List 2 - typically end of

discharge)

Accessories: External Ground Bar Assembly

Seismic Anchor Kits

Bullet-Style Fuse Holders, Fuses

Bullet-Style Circuit Breakers

2 ft Extension Cabinet for 9-ft application

4-1/2 ft Extension Cabinet for 11-1/2 ft applications

Top Cover for Bottom Feed Applications.