Discharge return bus options, Internal, External – GE Industrial Solutions BDCBB H569-445 User Manual

Page 29

Advertising
background image

Secondary DC Power Distribution Bay H569-445

Issue 3 June 2012

29

Discharge Return Bus Options

Discharge return bus options for terminating fuse or circuit breaker return leads may

either be internally mounted in the cabinet or externally mounted outside the

distribution bay on a cable rack.

Internal

The internal discharge return bus bar option terminates return cables from the battery

plant at the top (or bottom) of the cabinet as shown in Figure 12. There is a left-side bus

that interconnects to return bars mounted on the three left mounted fuse or circuit

breaker panels and a right-side bus for the right mounted panels. The bus at the top of

the cabinet is designed for terminating six 3/8 inch double-hole terminal lugs on 1 inch

centers with a tongue width up to 1.7 inches wide. Each panel mounted discharge

return bus is designed for terminating up to 2 gage cable with 1/4 inch double-hole

terminal lugs on 5/8 inch centers.

The advantage of internal returns is that load leads are paired at the fuse or circuit

breaker and eliminates the need for identification tags on each return lead. The

drawback to this cabling scheme is that you are limited to 1200 amps per side so for

multi-load BDFB’s requiring from 1200A-2400A capacity per side requires that input

returns must be located at the top and bottom of the cabinet with returns from the

battery plant split between the top and bottom bus bars. A second concern is the

potential cable congestion resulting from twice the number of leads in the distribution

bay. For these reasons, the internal discharge return option is recommended only for

applications with smaller ultimate capacities. For most applications, the external return

bus option is recommended.

External

The external discharge return bus bar options are shown in Figure 19 and Figure 20. The

external bus is mounted on a standard 15 or 20 inch ladder type cable rack. ED83019-50

Group 13 (150021156) and Group 13A (150021157) are rated for 2400 amperes of

current. Option 150021156 provides the first bus bar and the cable rack mounting

hardware. Option 150021157 provides a bus bar, the connecting bus bar and insulating

standoffs for stacking additional tiers as required. Refer to ED83019-50 drawing for

other ground bar options.