Installation, Operating and Maintenance Instruction

Model TVS


page 34

Meaning of code number for cause and method of repair
1.

Motor protection switch is wrongly set
• Check setting or replace the motor protection switch

2.

Phase failure
• replace defective safety fuses
• Check pipes for damage

3.

Wrong frequencies or under voltage
• Compare voltage and frequency with data on the rating plate

4.

Rotates in the wrong direction
• Swap over phases of power supply

5.

Motor winding or electrical cable defective
• Ask for assistance

6.

Motor gets caught at the star delta at the star stage
• Replace star delta converter

7.

Voltage loss due to burned out safety fuse
• Replace safety fuse

8.

Voltage loss due to defective feeding cables
• Renew cables

9.

Voltage loss due to motor protection switch being released
• Establish the causes
• Reset the motor protection switch

10. Pump is blocked due to impurities

• Dismantle and clean the pump part

11. Pump does not reach the handled liquid due to it not being installed deeply enough

• Check the water level
• Hang the unit deeper

12. Defective coupling

• Replace shaft and coupling

13. Gate valve closed

• open

14. Suction filter displaced by foreign bodies

• Take out pump and clean the suction filter

15. uninspected, wrong direction of rotation

• change direction of rotation

16. Gate valve not quite open

• open

17. Pipes constricted by foreign bodies

• clean pipes

18. Well filter blocked

• Consult well sinker company

19. Leakage in the delivery pipe

• Check pipes

20. Impellers worn because liquid handled is aggressive or contains sand

• Dismantle unit and replace the impellers (be careful when selecting material)

21. Impellers worn due to cavitation

• Check operating conditions

22. too little speed due to under voltage or wrong frequencies

• Check mains voltage and mains frequency

23. too little speed because running in 2 phases

• check electrical branch circuit connections and safety fuses

24. Flow rate too high or too low

• Adjust valve