Extended vent terminations, Optional concentric terminations, Hard water – John Wood Commercial - 300-400K BTU User Manual

Page 12: Circulation pumps, Insulation blankets, Breathing hazard - carbon monoxide gas

Advertising
background image

12

extended Vent terminations

The water heaters covered by this manual can be installed using

4 inch pipe for the intake air and/or vent piping up to a maximum

of 70 equivalent feet (21.3 m). The intake air and/or vent piping

can be extended up to 120 equivalent feet (36.5 m) by installing

6 inch pipe. See the Venting requirements on page 21.
The water heater ships from the factory with two (2) 4 inch

terminations that are 45° PVC elbows with a debris screen

installed. When 6 inch intake air or vent pipe is installed, factory

supplied 6 inch terminations must be used.
Contact your local distributor or call the parts department phone

number listed on the back cover of this manual to order 6 inch

termination(s).

optional concentric terminations

The water heaters covered by this manual can be installed in a

Direct Vent configuration using optional concentric terminations.
AJWSH130300 models installed using 4 inch vent/intake air

piping use the 4 inch concentric termination. AJWSH130300

models installed using 6 inch vent/intake air piping use the

6 inch concentric termination. AJWSH130400 models must

use the 6 inch concentric termination on all installations. See

Venting requirements on page 21 and Concentric Termination

Installation on page 26.
Concentric terminations must be ordered separately. Contact

your local distributor or call the parts department phone number

listed on the back cover of this manual to order.

• 4” Concentric Termination Part # 9006328005
• 6” Concentric Termination Part # 9006327005

hard water

Where hard water conditions exist, water softening or the

threshold type of water treatment is recommended. This will

protect the dishwashers, coffee urns, water heaters, water piping

and other equipment.
See Maintenance on page 60 for sediment and lime scale

removal procedures.

circulation pumps

A circulating pump is used when a system requires a circulating

loop or there is a storage tank used in conjunction with the water

heater. See the Water Piping Diagrams beginning on page 67

for installation location of circulating pumps.
See Circulation Pump Wiring Diagrams on page 66 for electrical

hookup information. Install in accordance with the current edition

of the National Electrical Code, NFPA 70 or the Canadian

Electrical Code, CSA C22.1.
All-bronze circulators are recommended for used with commercial

water heaters.
Some circulating pumps are manufactured with sealed bearings

and do not require further lubrication. Some circulating pumps

must be periodically oiled. refer to the pump manufacturer’s

instructions for lubrication requirements.

insulation blankets

Do not obstruct water heater air intake

with insulating blanket.
Gas and carbon monoxide detectors

are available.
Install water heater in accordance with

the instruction manual.

Breathing carbon monoxide can cause brain damage or

death. Always read and understand instruction manual.

Breathing Hazard - Carbon Monoxide Gas

Insulation blankets are available to the general public for external

use on gas water heaters but are not necessary with these

products. The purpose of an insulation blanket is to reduce the

standby heat loss encountered with storage tank heaters. The

water heaters covered by this manual meet or exceed the Energy

Policy Act standards with respect to insulation and standby heat

loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this

heater, you should follow these instructions. See the Features

and Components section of this manual for identification of

components mentioned below. Failure to follow these instructions

can restrict the air flow required for proper combustion, potentially

resulting in fire, asphyxiation, serious personal injury or death.

do not apply insulation to the top of the water heater, as

this will interfere with safe operation of the blower assembly.

do not cover the control system LCD on top of the water

heater.

do not cover the Temperature-Pressure relief Valve.
do not cover the instruction manual. keep it on the side of

the water heater or nearby for future reference.

do obtain new warning and instruction labels from the

manufacturer for placement on the blanket directly over the

existing labels.

do inspect the insulation blanket frequently to make certain

it does not sag, thereby obstructing combustion air flow.

Advertising