Supply gas line installation, Gas line sizing – John Wood Commercial - 300-400K BTU User Manual

Page 36

Advertising
background image

36

supply gas line installation

Contact your local gas utility company to ensure that adequate

gas service is available and to review applicable installation

codes for your area.
be sure that the gas meter has sufficient capacity to supply the

rated gas input of the water heater as well as the requirements

of all other gas fired equipment supplied by the meter. If the

gas meter is undersized, the gas company will have to install a

properly sized gas meter.

Fire and Explosion Hazard

Turn off gas lines during installation.
Contact a qualified installer or service

agency for installation and service.

Excessive gas pressure to gas valve can

cause serious injury or death.

Do not use water heater with any gas

other than the gas shown on the rating

label.

Make sure gas supplied is same type listed on the water heater’s

rating label.
The water heaters covered in this manual are not intended for

operation at higher than 10.0” W. C. (2.49 kPa) for natural gas

and 12.0” W. C. (2.99 kPa) for propane gas supply pressure, see

Table 3 on page 13. The water heaters covered in this manual

require supply gas regulators to maintain required supply gas

pressure. Exposure to higher gas supply pressure may cause

damage to the gas controls which could result in fire or explosion.

If overpressure has occurred such as through improper testing of

gas lines or malfunction of the supply system the water heater’s

gas valve must be checked for safe operation by a Qualified

Service Agency.
Ensure supply regulator vent lines and the safety vent valves are

protected against blockage. These are components of the gas

supply system, not the water heater. Vent blockage may occur

during ice storms.
It is important to guard against gas valve fouling from

contaminants in the gas ways. Such fouling may cause improper

operation, fire or explosion. If copper supply lines are used they

must be internally tinned and certified for gas service.

REGULATED GAS

SUPPLY LINE
MAIN GAS

SHUTOFF VALVE
TEE FITTING

PIPE CAP

SEDIMENT TRAP

(DIRT LEG)

figure 52

Ensure all gas pipe is clean on the inside before installation. To trap

any dirt or foreign material in the gas supply line a sediment trap

(dirt leg) must be installed as shown in Figure 52. The sediment

trap must be readily accessible and not subject to freezing

conditions. Install in accordance with the recommendations of

the local gas utility company.
gas line siZing

do not

use flexible gas piping.

Minimum required supply gas line sizes are shown in Table 4 on

page 13. Depending on the developed equivalent length and/

or the number of appliances connected to a common main, the

size of supply gas lines may have to be increased.
Size the supply/main gas line(s) in accordance with Table 7 or

Table 8. The values given in Table 7 and Table 8 are for straight

lengths of iron pipe at 0.5" W. C. (125 Pa) pressure drop, which

is considered normal for low pressure systems. Note that fittings

such as elbows and tees will add to the pipe pressure drop.
supply gas line siZing u. s. units

table 7

lENGTH

IN

FEET

NOrMAL IrON PIPE SIZES (INCHES)

INPuT IN THOuSANDS bTu/Hr

1 1/4” 1 1/2”

2”

2 1/2”

3”

4”

10

1400

2100

3960

6300

11000

23000

20

950

1460

2750

4360

7700

15800

30

770

1180

2200

3520

6250

12800

40

660

990

1900

3000

5300

10900

50

580

900

1680

2650

4750

9700

60

530

810

1520

2400

4300

8800

70

490

750

1400

2250

3900

8100

80

460

690

1300

2050

3700

7500

90

430

650

1220

1950

3450

7200

100

400

620

1150

1850

3250

6700

125

360

550

1020

1650

2950

6000

150

325

500

950

1500

2650

5500

175

300

460

850

1370

2450

5000

200

N/A

430

800

1280

2280

4600

supply gas line siZing metric units

table 8

lENGTH

IN

METErS

NOrMAL IrON PIPE SIZES (INCHES)

INPuT IN kW

1 1/4” 1 1/2”

2”

2 1/2”

3”

4”

3.0

410

615

1160

1845

3221

6735

6.1

278

428

805

1277

2255

4626

9.1

225

346

644

1031

1830

3748

12.2

193

290

556

878

1552

3192

15.2

170

264

492

776

1391

2840

18.3

155

237

445

703

1259

2577

21.3

143

220

410

659

1142

2372

24.4

135

202

381

600

1083

2196

27.4

126

190

357

571

1010

2108

30.5

117

182

337

542

952

1962

38.1

105

161

299

483

864

1757

45.7

95

146

278

439

776

1610

53.3

88

135

249

401

717

1464

61.0

N/A

126

234

375

688

1347

Advertising