Concentric termination installation, Concentric – John Wood Commercial - 300-400K BTU User Manual

Page 26

Advertising
background image

26

termination. use only Schedule 40 PVC to extend the 6 inch

concentric termination.
When shortening the length of the termination carefully

measure and cut the larger (intake air) pipe first. Cut the

same amount of pipe off of the smaller (vent) pipe.

10. Depending on which termination(s) is being installed go to 4

Inch Concentric Termination Installation on page 27 or 6 Inch

Concentric Termination Installation on page 28.

CONCENTRIC TERMINATION(S)

MUST BE A MINIMUM OF 10 FEET

(3 m) AWAY FROM ANY PARAPET,

VERTICAL WALL OR

STRUCTURE.

4 INCH CONCENTRIC TERMINATION

FLAT ROOF CLEARANCE

figure 24

6 INCH CONCENTRIC TERMINATION

FLAT ROOF CLEARANCE

CONCENTRIC TERMINATION(S)

MUST BE A MINIMUM OF 10 FEET

(3 m) AWAY FROM ANY PARAPET,

VERTICAL WALL OR

STRUCTURE.

figure 25

concentric termination installation

1. Determine which concentric termination will be installed.

AJWSH130300 models installed using 4 inch vent/

intake air piping use the 4 inch concentric termination.

AJWSH130300 models installed using 6 inch vent/intake air

piping use the 6 inch concentric termination. AJWSH130400

models must use the 6 inch concentric termination on all

installations, see Venting requirements on page 21.

2. Determine the location for the termination.

note:

roof termination is preferred since it is less susceptible

to damage, has reduced chances to intake contaminants and

vent vapors are less visible.

3. When installing a concentric termination vertically through the

roof; ensure that all exterior vertical clearance requirements

for the concentric termination, shown in Figure 27 on page

27 and Figure 30 on page 28, are being maintained. These

clearances and those cited by local and national codes must

be maintained.

4. When installing a concentric termination vertically through a

flat roof, the termination's vent cap must be a minimum of 10

feet (3 m) away from any parapet, vertical wall or structure as

shown in Figure 24 and Figure 25.
note:

If this required distance to a parapet, vertical wall or

structure cannot be maintained, standard terminations must

be used. See Vertical Termination Installation on page 23

5. When installing a concentric termination through a sidewall;

ensure that all exterior sidewall clearance requirements for

the termination, shown in Figure 49 on page 34, are being

maintained. These clearances and those cited by local and

national codes must be maintained.

6. When installing multiple concentric terminations vertically

through a roof or horizontally through a sidewall ensure the

required clearances between terminations and groupings of

multiple terminations are maintained. See pages 29 and 30 for

more information.

7. Cut a 5 inch (13 cm) diameter hole for 4 inch concentric

terminations or 7 inch (18 cm) diameter hole for 6 inch

concentric terminations where the they will pass through the

wall or roof.
note:

beware of concealed wiring and piping when cutting

through the wall or roof.

8. When installing multiple concentric terminations vertically

through the roof in the same location the termination caps

for all concentric terminations must be at the same height

measured from ground. See Multiple Concentric Termination

Arrangements on page 30.

9. Determine if the concentric termination will need to be

shortened or lengthened to accommodate required

clearances or to ensure all vent caps are at the same height

when installing multiple terminations vertically through the

roof in the same location.
See Figure 26 on page 27 and Figure 29 on page 28 for the

maximum and minimum lengths allowed for the 4 inch and 6

inch concentric terminations.
When extending the length of a concentric termination
do not

use couplings. The use of couplings will restrict

flow through the termination and may cause improper

combustion. The termination’s intake air and vent pipes must

be replaced with longer sections of the same pipe material

when extending the length of the termination.
use only SDr-26 pipe to extend the 4 inch concentric