Supply gas line connection – John Wood Commercial - 300-400K BTU User Manual

Page 37

Advertising
background image

37

gas line connection
1. The water heaters covered by this manual are shipped from

the factory with a 1 1/4” supply gas connection, see Table 1

on page 10. Short pipe nipples and reducer couplings are

factory installed to increase the size of the water heater’s 24

VAC gas Valve inlet, see Figure 53.

2. Connect the supply gas line to the water heater's 24 VAC

gas Valve in accordance with all applicable local and national

code requirements. do not use flexible gas piping.

FACTORY INSTALLED

1 1/4” x 1” REDUCER

COUPLING AND NIPPLE

FIELD SUPPLIED

SUPPLY GAS PIPING

1 1/4” NPT MINIMUM

SUPPLY GAS LINE CONNECTION

24 VAC

GAS VALVE

TO MAIN

BURNER
FLOW

figure 53

3. Apply thread sealing compounds (pipe dope/ Teflon tape)

sparingly and only to the male threads of the pipe joints. Do

not apply sealing compound to the first two threads. use pipe

dope or Teflon tape marked as being resistant to the action of

liquid petroleum (LP/propane) gases.

4. use only a smooth jaw adjustable wrench (such as a monkey

wrench) as a back up on the body of the 24 VAC gas Valve

when tightening the first pipe nipple into the body of the valve.
do not

use a standard pipe wrench (Stillson wrench) with

metal tooth jaws as this may permanently damage the valve.

5. use a standard pipe wrench (Stillson wrench) as a back

up on the first pipe nipple installed above when connecting

other fittings and pipe in the supply gas line to prevent the

24 VAC gas Valve on the water heater from twisting during

installation.

6. To prevent damage, care must be taken not to apply too

much torque when connecting the supply gas line to the

water heater.

7. Install a sediment trap (dirt leg) as shown in Figure 52 on

page 36.

8. Install a Main gas Shutoff valve in the supply gas line as

shown in Figure 52 on page 36.

note:

Should overheating occur or the gas supply fail to shut

off, turn off the Main gas Shutoff valve to the water heater.
gas line leak testing

Fire and Explosion Hazard

Leak test before placing the

water heater in operation.
Disconnect gas piping and main

gas shutoff valve before leak

testing.
Install sediment trap in

accordance with NFPA 54.

Use joint compound or Teflon tape

compatible with propane gas.

Any time work is done on the gas supply system perform a leak

test to avoid the possibility of fire or explosion.
1. For test pressures exceeding 1/2 psi (3.45 kPa) disconnect

the water heater and its Main gas Shutoff Valve from the

gas supply piping system during testing, see Figure 52

on page 36. The gas supply line must be capped when

disconnected from the water heater.

2. For test pressures of 1/2 psi (3.45 kpa) or less, the appliance

need not be disconnected, but must be isolated from the supply

gas line by closing the Main gas Shutoff Valve during testing.

3. Paint all supply gas line joints and connections upstream

of the water heater with a rich soap and water solution

to test for leaks. bubbles indicate a gas leak. Do not use

matches, candles, flame or other sources of ignition for

this purpose.

4. repair any leaks before placing the water heater in operation.

Advertising