maintenance schedule

table 13

component

operation

interVal

reQuired

Tank

Sediment

removal

Semi Annually

Flushing

Tank

Lime Scale

removal

Semi Annually

uN-LIME®

Anode rods

Inspection

Cleaning

Annually

Clean Scale

Deposits

T&P Valve

Test operation

Semi Annually

Test

Vent System

Inspection

Annually

Termination

Screens Clean

Reseal/Repair

draining and flushing

It is recommended that the water heater storage tank be drained

and flushed every 6 months to reduce sediment buildup. The

water heater should be drained if being shut down during freezing

temperatures. See Features And Components on page 7 for

the location of the water heater components described below.

Burn harzard.

Hot water discharge.

Keep hands clear of drain

valve discharge.

to drain the water heater storage tank:
1. Turn off the electrical supply to the water heater.
2. Turn off the gas supply at the Main gas Shutoff Valve if

the water heater is going to be shut down for an extended

period.

3. Ensure the cold water inlet valve is open.
4. Open a nearby hot water faucet and let the water run until the

water is no longer hot.

5. Connect a hose to the water heater drain valve and terminate

it to an adequate drain.

6. Close the cold water inlet valve.
7. Open the water heater drain valve and allow all the water to

drain from the storage tank.

8. Close the water heater drain valve when all water in the

storage tank has drained.

9. Close the hot water faucet opened in Step 4.
10. If the water heater is going to be shut down for an extended

period, the drain valve should be left open.

maintenance

general

keep water heater area clear and free from combustible

materials, gasoline and other flammable vapors and liquids. See

Locating The Water Heater on page 11.
Water heater maintenance includes periodic tank flushing and

cleaning, and removal of lime scale. The water heater should

be inspected and adjusted to maintain proper combustion.

See Initial Start up on page 49. A periodic inspection of the

venting system should be made. Where used, water circulating

pump(s) should be oiled according to the pump manufacturer's

recommendations.

precautions

Do not operate the water heater if it has

been exposed to or exhibits the following:

Flooding at or above the level of the burner or controls.

External damage.

Firing without water.

Sooting.

Do not operate the water heater until all corrective steps

have been made by a qualified service agent.

CAUTION

Never operate the water heater without first being certain it is

filled with water and a properly sized and rated Temperature-

Pressure relief Valve is installed in the relief valve opening on

the water heater. See Temperature-Pressure relief Valve on

page 15.

Explosion Hazard

Overheated water can cause

water tank explosion.

Properly sized temperature and

pressure relief valve must be

installed in the opening provided.

Should overheating occur or the gas supply fail to shut off, turn

of the Main gas Shutoff valve. See Figure 52 on page 36.
Water heater maintenance includes periodic tank flushing and

cleaning, and removal of lime scale. The water heater should

be inspected and adjusted to maintain proper combustion.

refer to the following table. A periodic inspection of the venting

system should be made. Where used, the water circulating

pump should be oiled according to the pump manufacturer's

recommendations.