Electrical connection, 1 connection with auma plug/socket connector, 2 delay time – AUMA Electric part-turn actuators SG 05.1 - 12.1_SGR 05.1 - 12.1 NORM User Manual

Page 10: 3 reversal time, Delay time 10, Electrical connection 10, Mounting to valve, Connection with auma plug/socket connector

Advertising
background image

7.

Electrical connection

Work on the electrical system or equipment must only be
carried out by a skilled electrician himself or by specially
instructed personnel under the control and supervision of such
an electrician and in accordance with the applicable electrical
engineering rules.

7.1

Connection with AUMA plug/socket connector

.

Check whether type of current, supply voltage, and frequency comply with

motor data (refer to name plate at motor).

.

Loosen bolts (50.01) (figure 3) and remove plug cover.

.

Loosen screws (51.01) and remove socket carrier (51.0) from plug cover

(50.0).

.

Insert cable glands or conduit fittings suitable for connecting cables

(The enclosure protection stated on the name plate is only ensured if properly

sealed connections are made).

.

Seal cable entries which are not used with sealed threaded plugs.

.

Connect cables according to order-related terminal plan.

.

The terminal plan applicable to the actuator is placed inside the terminal

compartment, the operation instructions are attached to the handwheel in a

weather-proof bag.

A special parking frame (figure C-2) for protection against touching the

uncoated contacts and against environmental influences is available.

7.2

Delay time

The delay time is the time from the tripping of the limit or torque switches to the

motor power being removed. To protect the valve and the actuator, we recom-

mend a delay time < 50 ms. Longer delay times are possible provided the oper-

ating time, output drive type, valve type, and the type of installation are consid-

ered.

We recommend to switch off the corresponding contactor directly by the limit or

torque switch.

7.3

Reversal time

Actuators operated via non AUMA supplied controls must include a minimum

reversal time delay of 100ms.

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1
AUMA NORM

Operation instructions

10

Figure C-1: Connection

50.0

50.01

51.0

51.01

Technical data

Power terminals

1)

Protective earth

Control terminals

No. of contacts max.

6 (3 are used)

1 (leading contact)

50 pins/sockets

Marking

U1, V1, W1, U2, V2, W2

1 to 50

Connecting voltage max.

750 V

250 V

Current max.

25 A

16 A

Type of customer connection

Screws

Screw for ring lug

Screws

Cross section max.

6 mm

2

(10 AWG)

6 mm

2

(10 AWG)

2.5 mm

2

(12 AWG)

Material:

Pin/socket carrier

Polyamide

Polyamide

Polyamide

Contacts

Brass (Ms)

Brass (Ms)

Brass, tin plated or gold plated (option)

1) Suitable for copper wires. For aluminium wires, please contact AUMA

Table 2: Technical data AUMA plug/socket connector

Figure C-2: Parking frame

(accessory)

Parking frame