Service conditions
Enclosure protection according

to EN 60 529

2)

Standard:

IP 67

Options:

IP 68

IP 67-DS (Double Sealed)

IP 68-DS (Double Sealed)

(Double Sealed = additional protection of the interior of the housing

against ingress of dust and dirt when removing the plug)

Corrosion protection

Standard:

KN

Suitable for installation in industrial units, in water or power plants

with a low pollutant concentration

Options:

KS

Suitable for installation in occasionally or permanently aggressive

atmosphere with a moderate pollutant concentration

(e.g. in wastewater treatment plants, chemical industry)

KX

Suitable for installation in extremely aggressive atmosphere

with high humidity and high pollutant concentration

KX-G same as KX, however aluminium-free version (outer parts)

Finish coating

Standard:

Two-component iron-mica combination

Standard colour

Standard:

Dark grey (DB 702, similar to RAL 9007)

Option:

Other colours are possible on request

Ambient temperature

3)

Standard SG:

– 20 to + 80 °C/ – 20 to + 175 °F (with 3-phase AC motor)
– 25 to + 70 °C / – 20 to + 158 °F(with 1-phase AC and DC motor)

Standard SGR:

– 25 to + 60 °C/ – 20 to + 140 °F (with 3-phase AC motor)

Options:

– 40 to + 60 °C – 40 to + 140 °F(low temperature)
– 50 to + 60 °C/ – 75 to + 140 °F (extreme low temperature)

(SG with 3-phase AC current only)

Lifetime

SG 05.1/SG 07.1:

20,000 operating cycles (OPEN - CLOSE - OPEN) for 90°

SG 10.1:

15,000 operating cycles (OPEN - CLOSE - OPEN) for 90°

SG 12.1:

10,000 operating cycles (OPEN - CLOSE - OPEN) for 90°

SGR 05.1 – 12.1:

4)

min. 2.5 million operations (control steps)

Other information
EU Directives

Electromagnetic Compatibility (EMC): (89/336/EEC)
Low Voltage Directive: (73/23/EEC)
Machinery Directive: (98/37/EC)

Reference documents

Product description “Electric part-turn actuators SG”

Dimension sheets SG

Electrical data SG/SGR

2) For version in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended Additionally, for enclosure protection IP 68, we recommend

to use the double sealed terminal compartment DS

3) Version with RWG min. – 40 °F (40 °C) and max. + 158 °F (70 °C)
4) The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To reach the longest possible

maintenance and fault-free operation time, the number of starts per hour chosen should be as low as permissible for the process

6

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1
AUMA NORM

Operation instructions