Setting the potentiometer (option), Potentiometer 20, Remote indication 20,21 – AUMA Electric part-turn actuators SG 05.1 - 12.1_SGR 05.1 - 12.1 NORM User Manual

Page 20: Setting the torque switching

Advertising
background image

16.

Setting the potentiometer (option)

— For remote indication —

.

Move valve to end position CLOSED.

.

Pull off indicator disc.

.

Turn potentiometer (E2) counterclockwise until stop is felt.

End position CLOSED corresponds to 0 %, end position OPEN to 100 %.

.

Turn potentiometer (E2) back a little.

Due to the ratio of the reduction gearings for the position trans-
mitter, the complete resistance range is not always utilized for
the whole travel. Therefore, an external possibility for adjust-
ment (setting potentiometer) must be provided.

.

Perform fine-tuning of the zero point at external setting potentiometer

(for remote indication).

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1
AUMA NORM

Operation instructions

20