Test run, 1 checking thedirection of rotation, 2 checking the limit switching – AUMA Electric part-turn actuators SG 05.1 - 12.1_SGR 05.1 - 12.1 NORM User Manual
Page 19: Test run 19, Setting direction close (black section), Setting direction open (white section), Checking the duo limit switches
15.
Test run
15.1 Checking the
direction of rotation
.
Place indicator disc on shaft.
The direction of rotation of the indicator disc (figure M) indicates the direction
of rotation of the output drive.
.
Move actuator manually to intermediate position or to sufficient distance from
end position.
.
Switch on actuator in running direction CLOSE and observe the direction of
rotation:
If the indicator disc turns clockwise, the direction of rotation is correct.
If the direction of rotation is wrong, switch off immediately
Correct phase sequence at motor connection. Repeat test run.
15.2 Checking the limit switching
.
Move actuator manually into both end positions of the valve.
.
Check whether limit switching is set correctly. Hereby observe that the appro-
priate switch is tripped in each end position and released again after the
direction of rotation is changed. If this is not the case, the limit switching must
first be set, as described from page 16.
If no other options (sections 16. to 18.) require setting:
.
Close switch compartment (see page 24, section 19.).
19
Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1
Operation instructions
AUMA NORM
Figure M: Indicator disc
OPEN