15.

Test run

15.1 Checking the

direction of rotation

.

Place indicator disc on shaft.

The direction of rotation of the indicator disc (figure M) indicates the direction

of rotation of the output drive.

.

Move actuator manually to intermediate position or to sufficient distance from

end position.

.

Switch on actuator in running direction CLOSE and observe the direction of

rotation:

If the indicator disc turns clockwise, the direction of rotation is correct.

If the direction of rotation is wrong, switch off immediately
Correct phase sequence at motor connection. Repeat test run.

15.2 Checking the limit switching

.

Move actuator manually into both end positions of the valve.

.

Check whether limit switching is set correctly. Hereby observe that the appro-

priate switch is tripped in each end position and released again after the

direction of rotation is changed. If this is not the case, the limit switching must

first be set, as described from page 16.

If no other options (sections 16. to 18.) require setting:

.

Close switch compartment (see page 24, section 19.).