7.4

Controls made by AUMA

In case the required reversing contactors are not to be installed in the control

cabinet, the controls AUMA MATIC or AUMATIC can easily be mounted to the

actuator at a later date.

For enquiries and more information, please state our commission no.

(refer to actuator name plate).

7.5

Heater

AUMA part-turn actuators have a heater installed as standard. To prevent

condensation, the heater must be connected.

7.6

Motor protection

In order to protect against overheating and extreme high temperatures at the

actuator, PTC thermistors or thermoswitches are embedded in the motor

winding. The thermoswitch is tripped as soon as the max. permissible winding

temperature has been reached.

Failure to integrate PTC thermistors or thermoswitches into the control circuit

voids the warranty for the motor.

7.7

Remote position transmitter

For the connection of remote position transmitters (potentiometer, RWG),

shielded cables must be used.

7.8

Limit and torque switches

Only the same potential can be switched on the two circuits (NC/NO contact) of

a limit or torque switch. If different potentials are to be switched simultaneously,

tandem switches are required.

To ensure correct actuator indicationss, the leading contacts of the tandem

switches must be used for that purpose and the lagging contacts for motor

switching off.

7.9

Fitting the cover

After connection:

.

Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with

screws (51.01).

.

Clean sealing faces at the plug cover and the housing.

.

Check whether O-ring is in good condition.

.

Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.

.

Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.

.

Fasten cable glands with the specified torque to ensure the required enclo-

sure protection.

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1

Operation instructions

AUMA NORM

11

RD

BK

RD

BK

BK

2

RD 2

BK

RD

BK

2

RD 2

BK

RD

TSC 1 / TSO 1
LSC 1 / LSO 1

TSC / TSO
LSC / LSO

DSR 1 / DÖL 1
WSR 1 / WÖL 1

DSR / DÖL
WSR / WÖL

Figure 4

I

Single switch

II

Tandem switch

SPDT

DPDT

Mechanical

life time = 2 x 10

6

starts

Type of current

Switch rating I

max

30 V

125 V

250 V

1-phase AC

(ind. load) cos phi = 0.8

5 A

5 A

5 A

DC

(resistive load)

2 A

0.5 A

0.4 A

with gold plated contacts

min. 5 V, max. 50 V

Current

min. 4 mA, max. 400 mA

Table 3: Technical data limit/torque switches

NO

NC

NC

NO