AVTECH Software Inc.

Installation

Room Alert 32W

NOTE: Manual discovery occurs over TCP port 30718. Please ensure this port is open and not blocked on your network.

If manual discovery is not possible or if there is not an entry in the DHCP server, follow the
instructions listed under the ‘Static-Only Networks’ subsection above.

If the Room Alert 32W unit is discovered although has a 169.254.xxx.xxx IP address, the Room
Alert 32W unit may not have been connected properly or DHCP assignment may currently be getting
blocked. In either case, follow the instructions listed in the ‘Static-Only Networks’ subsection above.

NOTE: If the above instructions do not allow discovery of the Room Alert 32W monitor, please initiate a Live Chat technical

support request on AVTECH.com or send an email support request to [email protected]. There are some scenarios that

will call for special procedures which cannot be accomplished with Device ManageR. In these unusual events, you will need the

AVTECH Device Discovery Utility. This utility is also available from the ‘Downloads’ section of our website. In the unlikely event

you fi nd yourself in one of the following situations, the AVTECH Device Discovery Utility will be needed to resolve your issue.

These situations would be a case where you cannot discover the Room Alert 32W with Device ManageR using either automatic

or manual discovery, although you need to update the fi rmware on the unit or the rare instance where you need to perform a

fi rmware recovery on your Room Alert 32W. For more information, please see the Advanced Topics section of this manual.

Step 4:

Connect Included Sensors

And Accessories

The graphics below identify the connection ports and channels of the Room Alert 32W ID monitor ID box
that are visible on the front and rear panels. Use these to connect the included sensors and accessories.

A

Digital Temperature Sensor — Connect the included AVTECH Digital
Temperature Sensor to one of the External Environment Sensor Channels
shown above (A). The Digital Temperature Sensor provides a real-time digital
temperature reading at the location of the temperature probe. Position the sensor
in the desired location, running the sensor cable back to the Room Alert 32W ID
box. DO NOT remove the red plastic cap from the tip of the sensor.

B

C

Wireless Antenna — Connect the included Wireless Antenna to the Antenna RPSMA
Connector (B) to enhance communication between the Room Alert 32W and
WiSH/WiSPR Sensors which can be located up to approximately 250´/350´

A.

B.