Schreiber Chillers 1055AC/RC HANDBOOK User Manual

Page 29

Advertising
background image

automatically choose the correct rotation sequence, either forward or reverse.

RUN HOURS (MAINTENCE key)

Displays the run hours for each compressor, pump and fan.

FACTORY SETTINGS- Password Protected

These parameters are discussed in the special maintenance section of the manual.

ALARM HISTORY

Displays the last 25 alarms. Use the UP key to scroll through each alarm. Every alarm is time

and date stamped.

Pressing the UP and DOWN arrows simultaneously will reset the alarm history.

DATE AND TIME (CLOCK key)

Set and displays the date and time.

SENSOR CALIBRATION

SENSOR CALIBRATION

Sets and displays calibration data for each sensor.

CURRENT: The current reading of the sensor.

OFFSET: If the sensor is off by a certain amount it can be corrected by adding or

subtracting offset.

MIN: The minimum scale value

MAX: The maximum scale value

*MIN and MAX for pressure sensors only

SENSOR ALARMS

Enables/Disables sensor alarms.

ENABLED: Sets and displays whether or not the sensor alarm is enabled.

DELAY: The time in seconds in which an alarm condition is ignored to prevent nuisance

trips.

DIG-IN CALIBRATION

Controls the digital inputs (switch inputs).

ENABLED: Sets and displays whether or not the input is enabled

CURRENT: The current state of the input

ALARM State: Sets the digital state which trips an alarm.