Control

US1

Highest set-value setting

Set-value limits 1 for operator

US2

Highest set-value setting

Set-value limits 2 for operator

S1C

Control function 1

in = inverted (Heating, humidifying)
dir = direct (cooling, dehumidifying)

S2C

Control function 2

in = inverted (heating, humidifying)
dir = direct (cooling, dehumidifying)

AC

Minimum switch-off period

0 ... 250 sec relay switch-off period

ouc

Dependency of the

diP = dependent (SET2 = SET1 + SET2)

set-values

ind = independent

on

Minimum switch-on period

0...250 sec relay switch-on period

ono

Minimum delay

0...120 min; minimum delay between two
activations of the control relay.

Alarms

ALC

Configuration

rE = relative to the set-value (in Kelvin)

Temperature alarm

Ab = absolute values (in °C)

ALL

Low temperature alarm

If SET - ALL undershot, a low tempe-
rature alarm will be triggered after the
delay time ALd.

ALU

Over-temperature alarm

If SET + ALU exceeded, a high tempe-
rature alarm will be triggered after delay
time ALd.

ALH

Hysteresis for the

Automatic alarm acknowledgement:

Limit value alarms

For high alarm, undershooting of

ALL and ALU

ALU - ALH and low alarm for exceeding
ALL + ALH

ALd

Alarm delay

Minimum time in which the conditions for

at temperature over/

Alarm situation must be present.

Undershoot (0...999 min)

dAO

Alarm delay at for

Suppression of alarms after

mains ON (0...23.5 h)

Commissioning

So1

Status of the control relay

oFF = opened

with sensor fault

on = closed

So2

S

Status of the control relay

oFF = opened

with sensor fault

on = closed