PID control (only Output 1 at Ft = PID)

Pb

Proportional range

Preset possibility only for Set-value 1

(°C or °F)

which affects the first control output.
This value determines the bandwidth
(on both sides of the set-value) that
exist within the proportional control.

int

integral action time

Determines the integral behaviour of the

(0...999 sec)

controller. The greater the deviation,
the higher the effect.

dEt

Derivative action time

Determines the differential behaviour of

(0...999 sec)

the controller. The greater the deviation,
the higher the effect.

Sr

Measurement rate

Time between 2 consecutive

(1...10 sec)

following measurements for the
calculation of dt. A smaller value
increases the response time.

rS

Manual Reset

With this parameter, the proporti-

(°C or °F)

onal control deviation can be moved up /
down.

The value will be defined as the

same amount, but in the opposite
direction to the deviation detected.

A r

Integralband

Range (on both sides of the set-value)

(°C oder °F)

within which the integral action time is
effective. The higher the value,
the greater the effect.

Cyt

Zykluszeit

Minimum time during which the out-

(1...500 sec)

put relay is switched on and off.

drb

Soft-start band

If the temperature is outside the band

(°C oder °F)

(on both sides of the set-value), a new
Soft-Start will be initiated.
(0 = deactivated)

dSi

Dynamic set-value

This value determines the stepwise

control (°C or °F)

set-value increase from SET1.
(0 = deactivated)

dSt

Clock time for dynamic

clock time for dynamic set-value-

set-value cpntrol

control with regard to dSi (SOFT-Start).
(1...999 sec)

NOTE

You can access hidden parameters by holding down the
buttons SET + for 3 seconds in the programming level HY.
The message Pr2 appears.