English, 8repair work 8.1 faults – Burkert Type TAT002 User Manual

Page 26

Advertising
background image

24 - 0911

english

ACKNOWEDGING ERRORS VIA THE KEYBOARD

Press any button.

The Alarm message remains on the display as long as the alarm conditions
are present. The device then switches to normal operation.

AUTOMATIC ACKNOWLEDGEMENT OF THE ERROR

Message

PFo and PFc - Room sensor error

After approx. 30 seconds or once the error has been cleared, the
message will be acknowledged automatically. Check the connections
before any replacement of the sensor.

Messages

HA/LA - High/Low temperature alarm

The messages disappear automatically as soon as the normal temperature
range is reached again or if defrosting starts.

External alarms EAL and BAL are acknowledged after deactivation of the
digital input.

STATUS OF THE ALARM RELAY

Device status

AS = CL

AS = OP

Device without power

5 - 6 closed

5 - 6 closed

Normal operation

5 - 6 closed

5 - 6 open

Alarm situation during

operation

5 - 6 open

5 - 6 closed

8

REPAIR WORK

8.1

Faults

ERROR MESSAGES

Message

Cause

Effect

PFo

Sensor defective or not
connected

Alarm relay ON; control circuit

according to So1

PFc

Sensor short-circuit

Alarm relay ON; control circuit

according to

HA

High temperature alarm

Alarm relay ON; outputs remain

unchanged

LA

Low temperature alarm

Alarm relay ON; outputs remain

unchanged

EAL

Digital input alarm

Outputs remain unchanged

BAL