8623 - 17

english

7.3.6 External default set-value (C.02)

For external default set-values, enter a scale limit with time units (see 7.3.5.1).

The flow range corresponding to the standard signal (4-20 mA) must be set.
I.e., the input of the flow at 4 mA (lower limit value) and at 20 mA (upper limit
value) takes place.

Î

Limit the lowest control range using the lower limit value

7.3.6.1 Lower limit value

Setting the pre-comma value of the lower limit value

Example:
Set K Factor:

4 pulses /l

gewünschter Sollwert:

199,99 l / s

=>

Frequency of the flow sensor:
f = Q * K

f

frequenz

= 199.99 l/s * 4 pulse / l

Q

Flow rate

= 800 Hz

K

K Factor

=>

f > 625 Hz, i.e., cannot be read in

=>

Set values that can be set: 0 - 156.25 l/s (corresponds to the
frequencies 0 - 625 Hz)

=>

For higher set-values, a sensor with a lower K factor must be
selected.

Example:

Lower limit value

0 l/min

4 mA

Upper limit value

180 l/min

20 mA

NOTE:

With external set-values (standard signals) the error message
E.06 appears as soon as a signal less than 4 mA is read in.

Increase of the pre-comma value

Proceed to set the post-comma
value