English, 9appendix 9.1 error messages – Burkert Type 8623 User Manual

Page 29

Advertising
background image

8623 - 27

english

9

APPENDIX

9.1

Error messages

Display Cause

Remedy

E.01

Sensor failure at the 1st frequency Check the flow sensor
input

E.02

Sensor failure at the 2nd frequency Check the flow sensor
input

E.03

Frequency 1 greater than 625 Hz

Replace the flow sensor

E.04

Frequency 2 greater than 625 Hz

Replace the flow sensor

E.05

Flow rate larger than 199.99, and
therefore can no longer be displayed

E.06

Standard signal outside 4 - 20 mA

Check the standard

range signal

E.07

The ratio demands a frequency

Change the raito or fit

greater than 625 Hz from the fre
quency input another flow sensor

E.08

The sensing ratio of the proportional
valve is greater than 95%

Table 1: Error messages