K factors (in pulse/litre) for screw-ons – Burkert Type S020 User Manual

Page 28

Advertising
background image

28

Technicaldata

Type S020

6.4.8. K factors (in pulse/litre) for screw-ons

When the dimensions of your pipe are slightly different from dimensions d and s given in the table, recalculate the K factor using one
of the formulae in chap. 6.4.2.

If the measuring device does not automatically convert the K factor, use the following conversion formulae before setting the para-
meters of the device:
• K factor in pulse/US gallon = K factor in pulse/litre x 3.785
• K factor in pulse/UK gallon = K factor in pulse/litre x 4.546

Table 22: K factors, external diameters and theoretical cross-sections of screw-ons

measuring device inserted

8020, 8024, 8025, 8026

8041, 8045

external diameters and theoretical

cross-sections

material of the pipe

pVc

pp / pe

pVc

pp / pe

d

pVc

[mm]

s

pVc

[mm]

d

pe/pp

[mm]

s

pe/pp

[mm]

dn

100

4,83 (L)

5,29 (L)

33,0 (L)

30,4 (L)

110

8,1

110

10

110

3,45 (L)

-

44,7 (L)

-

125

9,2

125

11,4

125

2,55 (L)

3,10 (L)

63,7 (L)

52,1 (L)

140

10,3

140

12,8

150

1,67 (L)

2,12 (L)

137 (L)

78,8 (L)

160

6,2

160

14,6

180

1,08 (L)

1,37 (L)

197 (L)

116 (L)

200

9,6

200

18,2

200

0,80 (L)

1,07 (L)

290 (L)

147 (L)

225

8,6

225

20,5

250

-

0,63 (L)

-

347 (L)

-

-

280

25,5

300

-

0,42 (L)

-

510 (L)

-

-

315

28,7

350

-

0,30 (L)

-

705 (L)

-

-

355

32,3

400

-

0,23 (L)

-

931 (L)

-

-

400

36,4

(L): long sensor version