Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 210

Advertising
background image




5-64

ADAM 4000 Series User’s Manual

4016

$AAS

Name

Start-up Voltage Output Configuration command

Description

Stores the present analog output value of the strain gauge
input module with address AA in the module’s non-volatile
register. The output value will take effect upon start-up or
after a brownout.

Syntax

$AAS(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the strain gauge input module whose analog
output is to be set.

S

is the Start-up Voltage Output Configuration command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AA(cr)

if the command is valid.

?AA(cr)

if an invalid command was issued.

There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.

!

delimiter character indicates a valid command was

received.

?

delimiter character indicates the command was invalid.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the strain gauge input module.

(cr)

is the terminating character, carriage return (0Dh).

NOTICE: A strain gauge input module requires a maximum of 6

milliseconds after it received a Startup Voltage Output
Configuration command to let the settings take effect. During
this interval, the module can not be addressed to perform any
other actions.

Advertising