Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 253

Advertising
background image

Digital I/O and Relay Output

Counter/Frequency Command Set


7-18 ADAM 4000 Series User’s Manual

$AAF

Name

Read Firmware Version command

Description

The command requests the digital I/O module at address
AA to return the version code of its firmware

Syntax

$AAF (cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

F

is the Read Firmware Version command.

(cr)

is the terminating character, carriage return (ODh).

Response

!AA(Version)(cr)

if the command is valid.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

(Version)

is the version code of the module’s firmware at

address AA.

(cr)

is the terminating character, carriage return (ODh).

4050, 4051, 4052, 4053, 4055,
4056S, 4056SO, 4060, 4068, 4069

Advertising